Effectively controlling the drum level in an industrial boiler helps to maximize overall energy efficiency. When the drum level varies it can not only impact boiler efficiency, but overall reliability due to unplanned shutdowns.

Mark Coughran Process Control Consultant

Mark Coughran
Process Control Consultant

Emerson’s Mark Coughran shared a story with me about a major North American university that was having difficulty with one of the boilers that supplies steam to the campus.

The drum level on this boiler has alarms at +4 and -4 inches of water. It will shut off the fuel on -6 inches of water. The preferred setpoint (SP) for efficiency is 0 inches of water.

However, due to a large cycle on the drum level process variable (PV), the operators preferred to raise the setpoint and live with frequent high PV alarms.

Boiler-Drum-Level-As-Found

Mark used the EnTech Toolkit, which showed that the boiler level process had an unusually sluggish response to changes in feedwater flow. The sluggish process response is not amenable to auto-tuning algorithms, trial-and-error, or shortcut tuning methods.

He noted that it is also difficult to control with a conventional proportional+integral (PI) controller; however, using derivative action (PID) can be tricky and is avoided by most people.

For these types of control issues, Mark and the Control Performance consultants recommend Lambda tuning. This tuning method provides a direct and systematic way to solve this type of problem.

Installing the Lambda tuning PID parameters immediately stopped the cycle. The operators were very pleased and have already begun experimenting with lower setpoints. The as-left data includes some firing rate changes, which are load disturbances to the drum level.

Boiler-Drum-Level-As-Left

If you’re unfamiliar with Lambda tuning, see a paper Mark wrote, Lambda Tuning — the Universal Method for PID Controllers in Process Control.

You can also connect and interact with other variability and control performance experts in the DeltaV and Ovation tracks of the Emerson Exchange 365 community.

Popular Posts

Comments

Follow Us

We invite you to follow us on Facebook, LinkedIn, Twitter and YouTube to stay up to date on the latest news, events and innovations that will help you face and solve your toughest challenges.

Do you want to reuse or translate content?

Just post a link to the entry and send us a quick note so we can share your work. Thank you very much.

Our Global Community

Emerson Exchange 365

The opinions expressed here are the personal opinions of the authors. Content published here is not read or approved by Emerson before it is posted and does not necessarily represent the views and opinions of Emerson.

PHP Code Snippets Powered By : XYZScripts.com